5 things to consider when specifying direct temperature monitoring for your transformer

11월 06 2020

 

Direct temperature monitoring (DTM) is a technology that has grown substantially over the last decade. The reasons for this are clear (find out more about the benefits of DTM by clicking here!) and are well known by end users. When it comes to specifying DTM, most end users do not know where and how to start. Most end users specify only the need for DTM and maybe the number of sensors. If a system is not specified properly, the end user may pay more or end up with a poor quality system based on old technology. The problem with DTM is that the sensors cannot be changed once installed—hence it is needed to accurately specify DTM in consideration of the entire lifetime of your transformer.

Below is a checklist for specifying your DTM.

1.  Number of sensors

The number of sensors has a direct impact on price for the whole DTM system. To choose the right number:

2.  Type of FO cable

Currently two types of FO cable are used for DTM, 200 μm and 62.5 μm, with 62.5 μm being the latest type. It was introduced in 2011 to meet IEC 60076-2 ANNEX E requirements, which were officially announced that same year. Make sure you specify the latest technology. 62.5 μm cable has the following benefits for end users: 

3.  FO bushings and plate

Now you need to get out with the FO cables from the transformer inside to the transformer outside. Therefore, the system on the right is used. The “bushings” are screwed into a plate. This is important to specify properly, because the bushings are a potential source of oil leakage that you will want to avoid.

4.  Monitor

The temperature-monitoring device is a main part of the whole DTM system. Specifying it is not too complicated since there are only a few things to consider:

Do you want a monitor with a screen? A screen lets you see the temperature of each sensor on site, at the transformer. If you only need to see temperatures in your SCADA system, specify no screen to save money.

If you need a screen, make sure it is possible to see all temperature values at once.

5.  Cite the IEC standard and parts of it

IEC 60076-2 ANNEX E clearly indicates what to consider when specifying FO temperature monitoring or so-called DTM. You should cite parts of the IEC 60076-2 ANNEX E standard in your specifications and also mention the standard itself. You may want to cite the following parts:

[1] Source: IEC 60076-2 ANNEX E

[2] Source: IEC 60076-2 ANNEX E

[3] Source: IEC 60076-2 ANNEX E